# ESP Delta 2002 # MAY 27 03 # new Valve manifolds # rev 012 # dry filter between fix exchanges # ~67 ml sample # depressurization stroke 2ml # fills puck with fix after dry-out # fix delays at 20 min EACH = 60 min total fix time # mod 5/27/03 for HAB/SSU WCR # mod 8/10/04 for new syringe # this one for non-pressure test PROGRAM: WCR_P SYRINGE PULL 5 Sample # prime puck DELAYSEC 45 SYRINGE PUSH ALL ToxicWaste # should be Waste for in situ SYRINGE PULL 7 Sample DELAYSEC 45 VALVEPORT Sample HOME SYRINGE PUSH ALL ToxicWaste #done depressurizing SYRINGE PULL 2.5 Fixative DELAYSEC 5 VALVEPORT Fixative HOME SYRINGEJOG PULL 2 SYRINGE PUSH 4 Puck # RINSE FILTER WITH FIX VALVEPORT Puck HOME VALVEPORT Syringe HOME SYRINGEJOG PULL 4 DELAYSEC 5 SYRINGE PULL 2 Air # air out puck DELAYSEC 10 VALVEPORT M3Bypass SET # relieve vacuum DELAYSEC 2 SYRINGE PUSH ALL ToxicWaste # puck cleared SYRINGE PULL 2 Fixative DELAYSEC 5 VALVEPORT Fixative HOME SYRINGEJOG PULL 2.5 SYRINGE PUSH 1.5 Puck VALVEPORT Puck HOME SYRINGEJOG PUSH 2.25 # fill filter holder DELAYSEC 20 # 1st fix VALVEPORT Puck SET DELAYSEC 10 # RINSE FILTER WITH FIX VALVEPORT Puck HOME VALVEPORT Syringe HOME SYRINGEJOG PULL 3.5 DELAYSEC 5 SYRINGE PULL 3 Air # air out puck DELAYSEC 10 VALVEPORT M3Bypass SET # relieve vacuum DELAYSEC 5 SYRINGE PUSH ALL ToxicWaste # puck cleared SYRINGE PULL 2 Fixative DELAYSEC 5 VALVEPORT Fixative HOME SYRINGEJOG PULL 2.5 SYRINGE PUSH 1.5 Puck VALVEPORT Puck HOME SYRINGEJOG PUSH 2.25 # fill filter holder DELAYSEC 20 # 2nd fix VALVEPORT Puck SET DELAYSEC 10 # RINSE FILTER WITH FIX VALVEPORT Puck HOME VALVEPORT Syringe HOME SYRINGEJOG PULL 3.5 DELAYSEC 5 SYRINGE PULL 3 Air DELAYSEC 10 VALVEPORT M3Bypass SET # relieve vacuum DELAYSEC 5 SYRINGE PUSH ALL ToxicWaste # puck cleared SYRINGE PULL 2 Fixative DELAYSEC 5 VALVEPORT Fixative HOME SYRINGEJOG PULL 2.5 SYRINGE PUSH 1.5 Puck VALVEPORT Puck HOME SYRINGEJOG PUSH 2.25 # fill filter holder DELAYSEC 20 # 3rd fix; total fix t=60 min VALVEPORT Puck SET DELAYSEC 10 # RINSE FILTER WITH FIX VALVEPORT Puck HOME VALVEPORT Syringe HOME SYRINGEJOG PULL 3.5 DELAYSEC 5 SYRINGE PULL 3 Air DELAYSEC 10 VALVEPORT M3Bypass SET # relieve vacuum DELAYSEC 5 SYRINGE PUSH ALL ToxicWaste # puck cleared SYRINGE PULL 5 Air # air out Puck x2 DELAYSEC 10 VALVEPORT M3Bypass SET # relieve vacuum in syringe DELAYSEC 5 SYRINGE PUSH ALL ToxicWaste END